Thankfully more and more new homes in Ontario are being 3rd party airtightness tested. Some do it to comply with EnerGuide80, some builders want to distinguish their build quality by having it ‘pass’ an air test or to meet a branded standard like EnergySTAR and many, surprisingly, still don’t get tested at all. Understandably many builders and architects are nervous about having their work tested, especially if it’s their first time, but working with a reputable Certified Energy Auditors (CEA) should allay those concerns if you approach the build systematically.

…I’ll huff and puff and blow your house down!

The truth is we’re not out to get you. Most CEAs share the builder’s desire to ensure better quality. In fact, many CEAs have been testing houses of all shapes sizes for many years and should be considered an asset. Over the past year, we’ve been working successfully with a handful of the best architect firms in the design phase to help iron out weak envelope details in the early design stages. We find the best results are realised through the Integrated Design Process (IDP) as all the key players come together early in the design phase to contribute expertise and share knowledge about the project well before ground is broken.

 

What’s an ACH50?

The conditioned air volume of the house, including the partition walls and floor cavities, are all part of the heated air volume of the house.  The “Air Changes per hour” (ACH) refers to how many times this equivalent whole air volume will be pushed out through the blower door at 50 Pascals of pressure difference between inside and outside the house. Century old homes generally leak air well over 10ACH and will lose more heat by air leakage than they do through the walls, whereas a new house under 3 ACH is considered “air tight” to the point of needing mechanical ventilation. The Passive House (PH) test method is different (pesky Germans!) in that it includes the conditioned air volume the volume occupied by the thickness of the exterior walls too.

 

Setting the bar

Most new houses can achieve air tightness levels of 2.5 – 4 ACH50 without putting a lot of attention to air barrier detailing. Most builders who take pride and know what to look for can hit 2 ACH fairly consistently. If you’re planning to have a house tested for the first time, consider talking to a CEA who can coach you along the way so that expectations are met, especially if you’re aiming to get under 2ACH. If aiming for anything lower than 2ACH, consider having he house tested BEFORE the drywall goes on. The EnergySTAR standard sets the bar at 2.0ACH or less, whereas the R2000 standard sets it’s minimum air leakage at 1.5ACH. The Passive House (PH) has the most stringent standard set at a mere 0.6ACH*.

 

Not all tests are alike

Broadly speaking there are two types of air tightness tests; an “As Is” and a “Canadian General Standards Board” AKA a “CGSB” test. The test is identical except that in the later, all intentional openings (fireplace flues, HRV vents, etc) are sealed up and as a consequence these test results are lower than ‘As Is’ tests. R2000, EnergyStar, HERS all require a CGSB test. EnerGuide tests are “As Is” test that are mostly done by depressurising the air from in the house, but can also be pressurised too. The PH test requires both a depressurisation and a pressurisation test to rule out bias due to unsealed flaps (clamp that seam!) in the air barrier.

 

It’s my first time…

On test day, some builders zip around nervously taping and sealing up joints in the air barrier, while others are resigned to a “let the chips fall where they may” attitude. The greatest opportunity for the builder is to have the site super and trades shadow the CEA during the test so they learn what to look for and how to treat the air barrier the next time they puncture a hole in it. The most common leakage points include missing attic hatches, doors without weather-strips, penetration leaks at the rim joists, fireplaces, and cold storage door frames that aren’t tied to the rough opening.

 

Preparing for the test…

If you’re doing a pre-drywall test, then the pressure’s off and you can note leaks by following the CEA around and seal them at your leisure later on. Ideally in pre-drywall tests, the sheathing on the outside of the house is the air barrier and if not acts as one to keep the volume of air leaking through walls low enough to prevent the poly from zipping off the walls. Ideally all ceilings to be insulated have their poly either supported by drywall, strips of resilient channel or 1”x3” strapping. If it’s the final test, then ensure all windows are cleaned and adjusted so they close and seal properly.

 

Occupancy

With careful attention to details, most tests go according to plan. Some tests don’t meet the target, but in most cases it’s due to obvious fixes, but some require extensive repairs and it is sad to see freshly painted drywall being ripped open to repair the envelop in a new house. The silver lining is that the occupant gets a higher quality product that’s more comfortable and cheaper to condition. As stated previously, hire and experienced consultant that can walk you through the process and check in periodically to ensure the target is within reach.

 

Come to our inaugural “High Performance Home Workshop” series!

On February 26th at 7PM, BGG will host a workshop covering the air barrier details that need to be addressed in order to successfully achieve the desired air tightness goal set out in the planning stages. It will be held at our offices on Spadina Ave at 7PM.

*This target air leakage rate was set for a multitude of good reasons. It is achievable, it cuts energy loss, increased envelope durability and it the level at which most PH designed homes can supply heat through mere ventilation ducts.

Views: 37

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Home Energy Pros

Home Energy Pros was founded by the developers of Home Energy Saver Pro (sponsored by the U.S. Department of Energy, under the American Recovery and Reinvestment Act) and brought to you in partnership with Home Energy magazine.

Latest Activity

Dennis Heidner commented on Macie Melendez's blog post Passive Proponent—Q&A with Brandon Weiss
"Don't forget Build America program from…"
11 minutes ago
John Wes joined James Sayers's group
Thumbnail

Marketing Energy Efficiency

Sharing ideas, tools and examples of promoting energy efficiency to consumersSee More
17 minutes ago
John Wes joined Tom White's group
Thumbnail

Weatherization

Share your concerns and successes as a weatherization professional, or information for this…See More
18 minutes ago
John Wes joined James Sayers's group
Thumbnail

Social Media and Energy Efficiency

Tell us how you reach customers, contractors and others using online social media.See More
19 minutes ago
John Wes joined allen p tanner's group
Thumbnail

Energy Auditing Equipment for Sale, Trade or to Purchase

Discuss the pros and cons of the equipment you are interested in prior to purchase. Post equipment…See More
21 minutes ago
Greg Whitchurch commented on Macie Melendez's blog post Passive Proponent—Q&A with Brandon Weiss
"Timothy,      For a start, you could…"
4 hours ago
Greg Traster posted a blog post

The Benefits Of Using Energy Star Shingles

In the harsh economic climate, saving money is of interest to everyone. Here is one method that you…See More
10 hours ago
Profile IconBryan Pringle, apexair, Emilian Karchev and 1 more joined Home Energy Pros
13 hours ago
Mark Richardson commented on Mark Richardson's group Renewable Energy
"Thanks Everblue, I am proud to say that I have also recently achieved the NABCEP Certified PV…"
13 hours ago
peter chang replied to peter chang's discussion Electrical system data loggers
"Thanks, this is proving very fruitful. I have a lot to learn but this will get me started in the…"
yesterday
Sandra K. Adomatis, SRA posted a blog post

Three WWWs to completing the Appraisal Institute’s Residential Green and Energy Efficient Addendum

The Residential Green and Energy Efficient Addendum is a form used to standardize the reporting of…See More
yesterday
William H Nickerson replied to peter chang's discussion Electrical system data loggers
yesterday

© 2013   Created by Lawrence Berkeley National Laboratory.

Badges  |  Report an Issue  |  Terms of Service