As I had brought up years ago, ACCA's Manual S was in dire need of an update.  Written in 1995, Manual S Residential Equipment Selection was passed by with huge technical and efficiency strides within the HVAC industry.  Think about it: ECM Motors were in their infancy, condensing furnaces were still prone to failures, and variable refrigerant flow was far from mainstream in the U.S.  All addressed in the updated Manual S! I have to say, their committee did a thorough job addressing updates to a process that is essential to system design and a code requirement in most of our country!  I highly recommend HVAC Sales Staff, System Designers, and Building Analysts purchase a copy of the new text, but in the meantime here is a teaser:

1.  Multi-Stage Central A/C: can be sized between .90 and 1.20 of the total building load.  This additional 5% of capacity vs. 1995 becomes increasingly important as homes get tighter and Sensible Heat Ratios rise.  Higher airflow to handle the increase in sensible loads lends to higher capacities.

2.  Variable Capacity Central A/C: can be sized between .90 and 1.30 of the total load.  See #1 for sensible capacity reasons, but variable capacity equipment is great for handling high latent capacities when operating on part load days as well.

3.  Cold Climate Heat-Pumps: can be sized to the total cooling building load + 15,000 btu/hr maximum.  This goes for single-stage, two-stage, and variable capacity equipment.  For mini-split heat-pumps, this 15K is above the total block load.

4.  Heat Pump Supplemental Electric Heaters: can be no larger than 5KW if the heat load is < 15,000 btu/hr.

5.  Fossil Fuel Burning Furnaces and Boilers: can be sized between 1.0 and 1.40 of the total heat load.  Ok, this isn't a change, just thought it was important to know!  If installing a furnace that needs a larger blower for cooling, maximum is now 2.0.

     Loaded with up to date examples, the new Manual S is far from a dust collector.  A great reference manual, but lets just hope it is not for another two decades like it's predecessor...but don't take my word for it!

Excess Air

Views: 98

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Eric Kjelshus on August 28, 2014 at 8:33am

I run loads each day.  BUT my completion does not,    I see so much over sizing  last job was needing 34,000 and he put in 120,000 BTU's ( the box fit)  I took out 1/2 the burners so the BTU fit the duct work and closer to the building.    My grand Pa would size 3 times needed or down to -40  so you could open the windows in bedrooms 8" to get "air" at night.   in the 1880 the gas was made from coal and was very high CO  when would burn,  some  Lights would be gas and CO in the building go high so would open window's to vent the home.    Gas was so cheap that was not metered  just so much a yr.

Home Energy Pros

Home Energy Pros was founded by the developers of Home Energy Saver Pro (sponsored by the U.S. Department of Energy,) and brought to you in partnership with Home Energy magazine.

Latest Activity

Paul Raymer's blog post was featured

What does it take to be a certified Home Energy Professional Quality Control Inspector (HEP QCI)?

A quality control program requires knowing a lot about a lot of different subjects.  A HEP (BPI…See More
8 hours ago
Bryan Pringle replied to Bryan Pringle's discussion Dense packed cellulose in basement?
"Can you tell me more about how the plastic makes the moisture worse?   I understand that in…"
11 hours ago
Profile IconMatthew Cooke, yasmine smith, myacand heat and 2 more joined Home Energy Pros
11 hours ago
Bryan Pringle replied to Bryan Pringle's discussion Dense packed cellulose in basement?
"I like cellulose because of its air leakage reduction property and the ease of making a quality…"
11 hours ago
Bryan Pringle replied to Bryan Pringle's discussion Dense packed cellulose in basement?
"This example is the reverse of my suggestion.  I would do high end vapor barrier against…"
11 hours ago
Al Heath replied to Bryan Pringle's discussion Dense packed cellulose in basement?
"Really?  Go back and read these posts again.... "play ground for mold."  I…"
12 hours ago
Mary Desilva posted blog posts
12 hours ago
Kim Tanner posted a video

Single Family Residential Air Leakage Testing

This session will cover the basics of air leakage testing on a single family home as well as issues that affect the accuracy and repeatability of the test. T...
12 hours ago

© 2015   Created by Lawrence Berkeley National Laboratory.

Badges  |  Report an Issue  |  Terms of Service