Vital to the operation of the refrigeration cycle, superheat must be maintained and stable to protect the compressor.  We all know that the heart of the system cannot compress liquid (slug) without bad things happening.  This would represent low/no superheat.  But, did you know high superheat can cause valve and compressor problems as well?  No matter the reason for attaching your gauges to the system, you must check the superheat, in the air-conditioning cycle.

Read More

Views: 551

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Bob Blanchette on January 16, 2014 at 2:12pm

Depends on type of system. TXV and Fixed orifices have different charging methods. As Steven stated airflow needs to be addressed, in many systems it falls WAY short. 3+ ton systems seem to be the worst offenders.

Comment by Steven Lewis on January 16, 2014 at 8:12am

Super heat readings without knowing airflow only gives you 1/2 the equation.  Dirty filters/ low airflow/refrigerant overcharge/low temp in building or low outdoor temp will all affect the superheat of the system.  If the superheat is out of range (high or Low) then the cause needs to be determined and corrected.  We all say that the house is a system but in HVAC  I say everything is Relative.  When you change one condition, it effects everything else, so it not the superheat temp but how it relates to the other information you gather.  As an example an A/C can have a high super heat of 20 if the indoor temp is high 88+ and outdoor temps are high as well and then when the unit has the house cooled down and running under normal conditions the superheat will be in normal range ( approx 8)  If you tried to charge the unit to reach the 8' you  would have vastly overcharged the system and dramatically raised its operating costs and shortened it life while making the homeowner uncomfortable as well.

Comment by Eric Kjelshus on January 10, 2014 at 6:34pm

I had a printer ask for just 2' superheat +-1'  to keep the paper very dry and never shut down the air handler/AC unit no case heater.    Most ask for 8'+ up to 30' superheat  next to the compresser.  so whats the deal?

Videos

  • Add Videos
  • View All

Twitter

Latest Activity

Simon joined Diane Chojnowski's group
Thumbnail

Online Training

Online training coursesIf you provide ongoing online training for home performance or…See More
9 hours ago
Simon added a discussion to the group Energy Auditing Equipment for Sale, Trade or to Purchase
Thumbnail

Wanted - Blower and door frame kit for Minneapolis system

Hi everyone,I'm new to this line of work and have bought some equipment (Minneapolis blower door…See More
16 hours ago
Simon replied to Steve Mann's discussion TEC Blower Door Frame in the group Energy Auditing Equipment for Sale, Trade or to Purchase
"Hi, I'm interested, but could you send to UK?,I'd pay shipping of course. My email is :-…"
17 hours ago
Simon replied to Jeffrey Anthony's discussion Blower Door Equipment - 9 shrouds, 10 fans, 5 fan controllers in the group Energy Auditing Equipment for Sale, Trade or to Purchase
"Hi, if you able to sell sepereately, I'd be interested in a blower and a frame kit. My only…"
17 hours ago
Simon joined allen p tanner's group
Thumbnail

Energy Auditing Equipment for Sale, Trade or to Purchase

Discuss the pros and cons of the equipment you are interested in prior to purchase. Post equipment…See More
17 hours ago
Simon is now a member of Home Energy Pros
21 hours ago
Rob Madden, Solar Home Broker joined Leslie McDowell, BPI's group
Thumbnail

Building Performance Institute (BPI)

BPI is the nation's premier standards development, quality assurance and credentialing organization…See More
yesterday
Rob Madden, Solar Home Broker posted a discussion

Indoor Air Quality Monitors and Meters

I'm considering purchasing the AirAdvice for Homes indoor air quality monitor but it seems to have…See More
yesterday

© 2016   Created by Lawrence Berkeley National Laboratory.   Powered by

Badges  |  Report an Issue  |  Terms of Service