Spot the Design Weakness - For Northern Climates

If we had a dime for each weak building assembly detail we saw, we’d be rich. In our 14 years of diagnosing comfort problems for clients; the exposed floor ranks as one of the most stark discomfort features of a home, new or old.

Walking home from the coffee shop Sunday and came across the feature below. Have a look at the photo and see how many design errors you can pick out:

Exposed floor with duct

1- The 2nd floor cavity is exposed above the front door.

2- The metal duct travels in a floor joist cavity past eh stone veneer covering a steel beam.

3- There are pot lights in the eaves.

Even 2LBS spray foam won’t ward off the discomfort in this small but significant exposed floor. How can it, the poor design will handicap it and soon enough all will be covered with lovely aluminum perforated soffit and who will know better.

So here’s the blow by blow, spray foam doesn’t stick well to oiled metal, there’s not enough room between the bottom of the duct and future soffit and though code does allow R12 they won’t get 2″ on the bottom. The duct will lose flow and warmth as it passes so close to the outdoors only to come back in. It runs close and may even touch 2 uninsulated metal beams. Lastly, let’s keep our finger’s crossed that the open joist cavity above the stone wall is continuously sealed otherwise that whole floor cavity above the entire foyer will feel cold to the touch on both sides (main floor and second).

As for the pot lights in the eaves, they are hard to change when they burn out and often create too much heat enough at times to create and ice dam.

Views: 1289

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by tedkidd on October 25, 2013 at 11:24am

Nice post Greg! 

Mind if I add to your list?  

4 - furnace will be oversized, so cycle times will be short thereby insuring that in heating season this duct will deliver cold air to a cold room. (You don't deliver hot air through cold duct.)

There is only so much you can do when multiple design flaws occur.  Often correcting for a few means the penalty due to the unsolvable (overhang) becomes insignificant.  I'd move the supply in as far as possible and use closed cell spray foam to this whole area.  

Videos

  • Add Videos
  • View All

Twitter

Latest Activity

Home Energy Magazine's blog post was featured
6 hours ago
Hannah Finch posted a blog post
6 hours ago
Profile Iconpank and Carrie Sturrock joined Home Energy Pros
6 hours ago
tedkidd commented on Amber Vignieri's blog post Chicago Winter No Match for Retrofitted Logan Square Building
"This case study is an example of how hard it is simply to do a compelling case study. Everyone has…"
8 hours ago
B. M. Lubin posted an event
Thumbnail

GPRO Construction Management Class at USGBC-LI headquarters in Hauppauge, NY at USGBC-LI Headquarters

September 19, 2016 at 9am to September 20, 2016 at 2pm
Taught by industry experts using real-life classroom exercises, GPRO CM gives experienced building…See More
12 hours ago
B. M. Lubin is now a member of Home Energy Pros
yesterday
Eric Kjelshus replied to tedkidd's discussion Dear DOE, PACE sucks - please fix or make it go away...
"Most HVAC system upgrade - change outs and attic seals-R-49 end up $20-30K   Most house -…"
yesterday
Brennan Less replied to Rob Madden, Solar Home Broker's discussion Indoor Air Quality Monitors and Meters
"Anyone interested in this realm should check out the EPA-funded project at the South Coast Air…"
yesterday

© 2016   Created by Lawrence Berkeley National Laboratory.   Powered by

Badges  |  Report an Issue  |  Terms of Service