Spot the Design Weakness - For Northern Climates

If we had a dime for each weak building assembly detail we saw, we’d be rich. In our 14 years of diagnosing comfort problems for clients; the exposed floor ranks as one of the most stark discomfort features of a home, new or old.

Walking home from the coffee shop Sunday and came across the feature below. Have a look at the photo and see how many design errors you can pick out:

Exposed floor with duct

1- The 2nd floor cavity is exposed above the front door.

2- The metal duct travels in a floor joist cavity past eh stone veneer covering a steel beam.

3- There are pot lights in the eaves.

Even 2LBS spray foam won’t ward off the discomfort in this small but significant exposed floor. How can it, the poor design will handicap it and soon enough all will be covered with lovely aluminum perforated soffit and who will know better.

So here’s the blow by blow, spray foam doesn’t stick well to oiled metal, there’s not enough room between the bottom of the duct and future soffit and though code does allow R12 they won’t get 2″ on the bottom. The duct will lose flow and warmth as it passes so close to the outdoors only to come back in. It runs close and may even touch 2 uninsulated metal beams. Lastly, let’s keep our finger’s crossed that the open joist cavity above the stone wall is continuously sealed otherwise that whole floor cavity above the entire foyer will feel cold to the touch on both sides (main floor and second).

As for the pot lights in the eaves, they are hard to change when they burn out and often create too much heat enough at times to create and ice dam.

Views: 1239

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by tedkidd on October 25, 2013 at 11:24am

Nice post Greg! 

Mind if I add to your list?  

4 - furnace will be oversized, so cycle times will be short thereby insuring that in heating season this duct will deliver cold air to a cold room. (You don't deliver hot air through cold duct.)

There is only so much you can do when multiple design flaws occur.  Often correcting for a few means the penalty due to the unsolvable (overhang) becomes insignificant.  I'd move the supply in as far as possible and use closed cell spray foam to this whole area.  

Videos

  • Add Videos
  • View All

Twitter

Latest Activity

Steven Lefler posted a status
6 hours ago
Ryan T De La Rosa is now a member of Home Energy Pros
7 hours ago
Chris Dorsi posted a blog post

My Favorite Announcement of the Year

Each year, Habitat X engages in…See More
8 hours ago
R Higgins replied to Energy Wise Solutions's discussion No Utility Homes, Are we ready to start building Homes that are not connected to traditional utilities ?
"First off, check the laws in your area.  Drought prone areas often prohibit on site collection…"
16 hours ago
R Higgins commented on Tom White's video
Thumbnail

Building Science Insights -- To Vent or Not to Vent

"Great lecture, kept thinking, but what about existing buildings.  Too little room at eaves for…"
17 hours ago
Luis Imery added a discussion to the group Job Board
Thumbnail

Hiring: Construction Manager with High Performance Custom Home Experience

POSITION DESCRIPTIONJob Title: Construction ManagerDepartment: Construction –…See More
yesterday
Profile IconLuis Imery and Quinn Korzeniecki joined Diane Chojnowski's group
Thumbnail

Job Board

This group is for posting jobs related to all aspects of the home performance industry including…See More
yesterday
Colin Genge posted an event

Retrotec is attending the NEBB Testing and Balancing (Tab) Certified Professional Review Seminar in Chicago, IL at Hilton Chicago O’Hare Airport

June 6, 2016 at 8am to June 8, 2016 at 5pm
Building owners and tenants are concerned that the environmental performance of buildings must be…See More
yesterday

© 2016   Created by Lawrence Berkeley National Laboratory.   Powered by

Badges  |  Report an Issue  |  Terms of Service