Ridge Vent . . . and Nothing But the Ridge

Can anyone convince me that this picture shows anything other than the fact that the ventilation provided here is effective only in the first five inches down from the ridge? And yes, there is continuous soffit venting that is baffled and open to the outside.

Views: 12028

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Bob Mariani on December 29, 2011 at 3:30pm

Still more natural air flow should persist.  I believe the soffit venting is insufficient.  The air movement should be equal between the ridge and the soffit vents.

Comment by Ed Voytovich on December 29, 2011 at 2:55pm

Bob . . . I'll refer to the black snot as "mildew" in hopes of assuaging to the extent possible the anxiety of the homeowners and the desire of their lawyers for a new Mercedes.   

Thanks for pointing out the fact that the cut-out is somewhere around an inch or less on each side instead of the manufacturers' recommended inch and a half.  Still, could another 3/4" on each side make that great a difference?

There are no gable end vents, and the same pattern of mildew extends the entire length of the ridge.

I suspect that this condition is more typical than not of ridge vents.  When the wind blows across the roof  and the ever-popular Bernoulli's Law (http://scienceworld.wolfram.com/physics/BernoulliEffect.html) comes into play, the downwind side of the vent sucks air out of the attic.  I suspect that it is most likely to take the makeup air from the nearest source (which is the other side of the ridge) than from either gable vents or vents in the soffit.  My thinking is that the high-moisture conditions in this particular house created an interesting experiment, but I am grateful for other thoughts and possibilities.

Comment by Bob Mariani on December 29, 2011 at 1:52pm

Ed, is that mold on the discolored section of the sheathing?  The vent opening should have been larger.  Only a small air flow is occurring.  Also be sure no gable vents are still opened that will short circuit the soffit to ridge vent airflow.

Videos

  • Add Videos
  • View All

Twitter

Latest Activity

Derrick Koehn commented on Diane Chojnowski's group Facebook Pages
2 hours ago
Derrick Koehn joined Diane Chojnowski's group
Thumbnail

Facebook Pages

Does your company or organization have a Facebook Page?This group is for pros who have facebook…See More
2 hours ago
Derrick Koehn posted a video

Tips on Wood Preparation & Use - Heatmaster SS G-Series

A few tips to get the most energy out of your wood using an outdoor wood stove. http://www.pineviewwoodstoves.com http://www.heatmasterss.com
2 hours ago
Paul Raymer posted a blog post

Zonal Pressure Puzzle

I have a wonderful little (16 x 14 x 8) test cabin at Bristol Community College in Fall River, MA. …See More
9 hours ago
Sarah Holloway posted a blog post

Play Game of Homes, by EnergyLogic, Inc.

I'd like to introduce everyone to Game of Homes, our cutting edge scenario based training tool…See More
10 hours ago
Nate Adams replied to Rob Madden, Solar Home Broker's discussion Indoor Air Quality Monitors and Meters
"Rob, I've bought, borrowed, or been given a number of different monitors. I had an Air Advice…"
14 hours ago
tedkidd replied to Rob Madden, Solar Home Broker's discussion Indoor Air Quality Monitors and Meters
"Yep, steep price but you will learn a lot. We are hoping these new devices that homeowners can own…"
15 hours ago
tedkidd replied to Luis Hernandez's discussion ERV Configuration
"We don't recommend ERV's anymore. If you are in a green grass climate ventilating…"
15 hours ago

© 2016   Created by Lawrence Berkeley National Laboratory.   Powered by

Badges  |  Report an Issue  |  Terms of Service