Ridge Vent . . . and Nothing But the Ridge

Can anyone convince me that this picture shows anything other than the fact that the ventilation provided here is effective only in the first five inches down from the ridge? And yes, there is continuous soffit venting that is baffled and open to the outside.

Views: 8371

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Bob Mariani on December 29, 2011 at 3:30pm

Still more natural air flow should persist.  I believe the soffit venting is insufficient.  The air movement should be equal between the ridge and the soffit vents.

Comment by Ed Voytovich on December 29, 2011 at 2:55pm

Bob . . . I'll refer to the black snot as "mildew" in hopes of assuaging to the extent possible the anxiety of the homeowners and the desire of their lawyers for a new Mercedes.   

Thanks for pointing out the fact that the cut-out is somewhere around an inch or less on each side instead of the manufacturers' recommended inch and a half.  Still, could another 3/4" on each side make that great a difference?

There are no gable end vents, and the same pattern of mildew extends the entire length of the ridge.

I suspect that this condition is more typical than not of ridge vents.  When the wind blows across the roof  and the ever-popular Bernoulli's Law (http://scienceworld.wolfram.com/physics/BernoulliEffect.html) comes into play, the downwind side of the vent sucks air out of the attic.  I suspect that it is most likely to take the makeup air from the nearest source (which is the other side of the ridge) than from either gable vents or vents in the soffit.  My thinking is that the high-moisture conditions in this particular house created an interesting experiment, but I am grateful for other thoughts and possibilities.

Comment by Bob Mariani on December 29, 2011 at 1:52pm

Ed, is that mold on the discolored section of the sheathing?  The vent opening should have been larger.  Only a small air flow is occurring.  Also be sure no gable vents are still opened that will short circuit the soffit to ridge vent airflow.

Home Energy Pros

Home Energy Pros was founded by the developers of Home Energy Saver Pro (sponsored by the U.S. Department of Energy,) and brought to you in partnership with Home Energy magazine.  Home Energy Pros is sponsored by the Better Buildings Residential Network.

Latest Activity

Bachi Brunato joined Kyle Brown's group
Thumbnail

Wrightsoft - Manual J / Manual D

If you use Wrightsoft to calculate loads or design ducts, you likely have questions.  Get answers…See More
3 hours ago
Colin Genge commented on Greg Labbe's blog post Technical Tape Desecration
"i don't have a picture of it, but my Honda Accord's windshield was replaced and it leaked…"
8 hours ago
terry nordbye replied to Jim Gunshinan's discussion PHIUS+2015 Climate-Specific Passive Building Standard
"Both standards are good. Both standards win. PHI knows how to build a PH in the USA. The very…"
12 hours ago
Greg Labbe replied to Jim Gunshinan's discussion PHIUS+2015 Climate-Specific Passive Building Standard
""It’s important to note that the PHIUS+ 2015 metric is an optimization of the European…"
12 hours ago
Melissa Ulbricht posted a blog post
13 hours ago
David M Cohen added a discussion to the group Job Board
14 hours ago
David M Cohen joined Diane Chojnowski's group
Thumbnail

Job Board

This group is for posting jobs related to all aspects of the home performance industry including…See More
14 hours ago
Profile IconSarah Mostafa, Michael Kelemen, Sean Maxwell and 3 more joined Home Energy Pros
14 hours ago

© 2015   Created by Lawrence Berkeley National Laboratory.

Badges  |  Report an Issue  |  Terms of Service