4 or 5 ton systems should be multi-stage...

Despite the passing of Regional Efficiency Standards, International Code requirements for Load Calculations and Equipment Selection, tighter homes and duct systems, I cannot see the likelihood of grossly over-sized equipment going down!  The significant problem at hand is that HVAC Contractors are either going to use the system design process, or not.  

In the meantime, Regional Standards are pushing Manufacturers into finding ways to make their systems more efficient.  Other than variable refrigerant flow (VRF), I am not sure what a manufacturer can do to increase the Energy Efficiency Ratio (EER).  In fact, some manufacturers and distributors have reported their variable capacity systems have actually tested, in a laboratory, lower EER than their two-stage and even single-stage counterparts.  We have seen the increased use of Electronic Expansion Valves (EEV) to maintain the lowest possible superheats in the industry.  Even increasing the physical size of Evaporator and Condenser coils in attempts to pick up/reject more heat.  This is all putting the burden on the contractor to find the room for installation, as well as finding systems that can deliver the latent capacity needed in the replacement market.

     So, I propose this: Why don't we require any 4 or 5 ton system be multiple stage or variable capacity?  This can address the significant over-sizing issue so often seen in the HVAC Industry.  After all, a study completed in 2006 by the Florida Solar Energy Center: "Measured Impacts of Proper Air Conditioning Sizing..." found little electrical savings for homeowners when replacing systems 47 - 65% oversized.  There is still significant peak energy savings to Electric Providers, hence the enforcement of proper sizing with most Utility Rebate Programs.  I wonder what those savings to the homeowner would have been if they just installed a multi or variable capacity system?  This code enhancement could change the industry significantly in future years, keeping the focus away from bigger coils and higher efficiency, but still pushing the contractor to proper sizing and equipment commissioning.  Yes, two-stage equipment costs more!  So you should size the equipment correctly to avoid these extra costs, increasing your bids.  Trust me, I have inspected as much as hundreds of A/C installations a year, for almost five years now, in a local utility rebate program.  Almost never do I see an installation or replacement system larger than a 3-ton.  Less than 10% of my inspected systems are larger, and almost always multi or variable capacity.  Customers still report increased comfort and reduced energy use.  Let's push efficiency using correctly sized, multiple capacity for the 4 or 5 ton systems, not physically larger units!

Views: 292

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Dennis Heidner on December 6, 2013 at 12:35am

The FSEC studies are good,  but using a 2006 study seven or eight years later when newer technology exists and had not been factored into the older study - may add some bias.

Did you really mean "keeping the focus away from bigger coils and higher efficiency"   right sizing the capacity should not mean downsizing the efficiency.  You really want the right capacity with the most efficient unit if you are trying to maximize the energy reductions.  If the point is to optimize the cost - unfortunately that might mean to oversize the system...(cheapest system). and then quickly sell and move out of the house :-)

Comment by Bob Blanchette on December 5, 2013 at 6:45pm

I question the study of replacing the oversized systems. Often ductwork is WAY too small and the oversized systems is not delivering it's rated capacity. Putting in a smaller unit matches the smaller ductwork better, and the savings are more significant than the study shows.

Comment by Christopher Morin on December 5, 2013 at 6:04pm
Thanks Bob! I couldn't agree with you more! If you need a furnace that big, you should probably zone with equipment or fix the envelope...
Comment by Bob Blanchette on December 5, 2013 at 5:42pm

While we're at it lets quit doing furnaces over 80k. Very few regions of the country require a furnace over 80k, most regions can go with a 40-60k in all but the largest homes. Yet 80-100k furnaces are routinely installed when heat less is 1/2 to 1/3 of that. High limits trip, heat exchangers crack, customer complain about wide temperature fluctuations.

Don't get me started on ductwork that rarely delivers the the high BTU performance of these monster sized HVAC units !!

Home Energy Pros

Home Energy Pros was founded by the developers of Home Energy Saver Pro (sponsored by the U.S. Department of Energy,) and brought to you in partnership with Home Energy magazine.

Latest Activity

Richard Beyer replied to Howard Katzman's discussion UV lights on filters
"Howard, There are numerous manufacturer's who swear these systems work and then you have the…"
6 hours ago
Christopher Morin posted a blog post

How do You Test a TXV?

  Thermostatic Expansion Valves (TEV or TXV), one of the most popular metering devices for…See More
10 hours ago
Howard Katzman posted a discussion

UV lights on filters

 recently saw UV bulb installations in 2 HVAC systems in a home. Each system had the Lennox Healthy…See More
12 hours ago
Don Fitchett joined Michael Stuart's group
Thumbnail

INFRARED THERMOGRAPHY USERS

This group is dedicated to knowledge sharing and discussion of infrared thermography for building…See More
12 hours ago
Don Fitchett commented on Diane Chojnowski's group Pinterest
"While most of our (BIN95.com) energy post and boards are industrial related, there are crossovers…"
12 hours ago
Don Fitchett joined Diane Chojnowski's group
Thumbnail

Pinterest

Do you have a Pinterest board for energy topics?Post the link to your Pinterest energy board in the…See More
12 hours ago
Profile IconJosh Guenther, Deborah Green, Kenneth Brooks and 3 more joined Home Energy Pros
13 hours ago
Jim Gunshinan commented on Jim Gunshinan's blog post My Energy Upgrade California—The Numbers Are In
"Hi David, to answer one question, the crawlspace was covered with thick poly and the seams were…"
13 hours ago
David Eakin commented on Jim Gunshinan's blog post My Energy Upgrade California—The Numbers Are In
"Jim, Maybe a little more detail on the project is in order. You say that your crawlspace is now…"
14 hours ago
Jim Gunshinan commented on Jim Gunshinan's blog post My Energy Upgrade California—The Numbers Are In
"Ed, no problem, I caught your meaning. Ted, I made a judgement that a mini split would be the best…"
14 hours ago
tedkidd commented on Jim Gunshinan's blog post My Energy Upgrade California—The Numbers Are In
"That makes sense.   What are your criteria/metrics for determining what might be the…"
14 hours ago
Ed Voytovich commented on Jim Gunshinan's blog post My Energy Upgrade California—The Numbers Are In
"Yikes!  Not only did I misspell "roof" as "rood," I also meant to more…"
14 hours ago

© 2014   Created by Lawrence Berkeley National Laboratory.

Badges  |  Report an Issue  |  Terms of Service