Ever since the adoption of the 2009 International Residential Energy Conservation Code (IECC), duct sealing efforts have been tested using the total leakage or leakage to outdoors methods.  It really is amazing how much duct gains effect the operation of your equipment and the comfort of your customer.  The missing part of "duct testing" appears to be how well the ducts are insulated.  Sure, you are required to use R-8 insulation on supply ductwork when located outside the building envelope, but how do we know it was installed correctly?  We're not required to test like the duct leakage codes, so is a check in the box sufficient?  How about we use some simple math to figure the gains, or lost capacities in cooling, and hold everyone to a standard - check out the equation below.

Sensible Btu/hr = CFM x Delta T x 1.08
   So, based on this math, one can take a few simple temperature measurements and calculate the lost sensible capacities due to duct leakage and insulation.   You should measure the temp of the air entering the return grille and at the unit to figure the return gain in sensible temperature.  I would also recommend averaging the temp readings at the furthest supply register, an average supply register, and a close one to figure the delta T from the air exiting the coil or air handler.  Do the same for an extensive return system.


  When you start measuring, it is very scary what you start to find.  As you can see, like the industry accepted national average, this system is losing 30% of the 3-ton capacity through it's well sealed, but poorly insulated duct system.  Unfortunately, the method is not perfect since a hotter day in the attic could cause greater gains.  But, that would be the time to sell duct sealing and insulation to the homeowner!  Any of you energy auditors out there could probably comment on how much attic ducts effect home infiltration as well.  So, why do we hate R-8 insulation?  Is it really just the hassle of wrapping the equivalent of a blanket around the ducts?  I don't recommend retrofitting a distribution system in an attic in the middle of July, but maybe it makes sense to offer to come back in the Fall?  Please, don't just leave it be!  Doing so makes it hard for this tree hugger to sleep at night!

http://excessair.blogspot.com/2012/06/duct-gains-why-do-we-hate-r-8...

Views: 465

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Bob Blanchette on June 29, 2012 at 6:44pm

The best bet is to reduce duct surface area if you can't get the ductwork into conditioned space. Have fewer registers and larger ductwork instead of lots of registers with small ductwork. Use truck/branch instead of '"ductopus". Keep runs short as possible. Eliminate runs to small/lightly used spaces. Put registers on sidewalls closer to the air handler, set sidewall registers to blow out into room.

The return isn't as big of an offender as the supply. As long as return is tightly sealed the wetbulb temperature won't change much. Wetbulb determines evaporator load. Then there is doing what you can to reduce attic temps, the best solution is typically large area passive vents. If you can see light coming through while in the attic, it's working...

Home Energy Pros

Home Energy Pros was founded by the developers of Home Energy Saver Pro (sponsored by the U.S. Department of Energy,) and brought to you in partnership with Home Energy magazine.

Latest Activity

Robert Leone added a discussion to the group Energy Auditing Equipment for Sale, Trade or to Purchase
Thumbnail

Blower Door Package for Sale

Hi,I am selling my blower door with extras as a package or individually. These items are used but…See More
2 hours ago
Profile IconRobert Leone and Richard Vito joined allen p tanner's group
Thumbnail

Energy Auditing Equipment for Sale, Trade or to Purchase

Discuss the pros and cons of the equipment you are interested in prior to purchase. Post equipment…See More
2 hours ago
Richard Vito joined Sean Lintow Sr's group
Thumbnail

Best Practices (Residential)

Best Building, Retrofitting, or even Auditing Practices - what are they, what should change, what…See More
10 hours ago
Richard Vito joined James Sayers's group
Thumbnail

Marketing Energy Efficiency

Sharing ideas, tools and examples of promoting energy efficiency to consumersSee More
10 hours ago
Richard Vito joined Allison A. Bailes III's group
Thumbnail

HVAC

HVAC design, Manuals J, S, T, & D, Duct leakage, Air flow, ENERGY STAR new home requirements,…See More
10 hours ago
Richard Vito joined Kyle Brown's group
Thumbnail

Wrightsoft - Manual J / Manual D

If you use Wrightsoft to calculate loads or design ducts, you likely have questions.  Get answers…See More
10 hours ago
Jim Gunshinan commented on Jim Gunshinan's blog post Energy Upgrade California—Up Close and Personal
"I had a revelation while attending Bruce Manclark's session of duct leak testing at the Energy…"
yesterday
George J. Nesbitt commented on Jim Gunshinan's blog post Energy Upgrade California—Up Close and Personal
"Blower Door; the 2007 test was a depressurization test, and the 2014 a pressurization test, which…"
yesterday
George J. Nesbitt replied to Kaushal Bharath Raju's discussion Affordability & Deep Energy Upgrade/Passive House Retrofit in Berkeley, California.
"Plan, plan, plan, plan. The 1st step to is to understand the house, how it's built, the…"
yesterday
George J. Nesbitt posted an event

High Performance Windows - A Panel of Experts at Pyramid Alehouse`

April 26, 2014 from 3pm to 5pm
Join a lively panel discussion on high performance windows. We'll cover some basics, as well as…See More
yesterday
Kaushal Bharath Raju replied to Kaushal Bharath Raju's discussion Affordability & Deep Energy Upgrade/Passive House Retrofit in Berkeley, California.
"Hi David, Thanks for pointing out Martin Holiday's article. I do not wish to engage in the…"
yesterday
Profile IconAdam Penberthy, Scot Davidson and j jarvella joined Home Energy Pros
yesterday

© 2014   Created by Lawrence Berkeley National Laboratory.

Badges  |  Report an Issue  |  Terms of Service