Replaced my A/C this weekend, results of downsizing by 1/3.

Recently my 13 yr old Carrier A/C devolved a leak and I chose to replace the system rather than track down the leak and repair the coil. I had been reading about doing manual J calculations and how contractors are scared to death to undersize. I had been talking to co-workers about this and it's an uphill battle getting them to think different than 1 ton per 500sq ft. So I decided to take confidence in correct sizing and "put my money where my mouth is" and install a 2 ton sized A/C.

House: 1587sq ft located in Oklahoma City, built 1999.
OLD A/C: Carrier 3 ton 12SEER system original to the house.
New Condenser: Thermalzone (Rebadged Rheem/Ruud) 2 ton 14.5 SEER.
New coil: 2 ton RFCL 13-16SEER with TXV

Results:
Temperature the old unit cycled until it was above 105, clearly oversized for our area. New 2 ton unit can keep 76F inside with a 100 degree outdoor temperature, but runs continuously to do so.
Humidity is HIGHER in the day with the new system even though it runs more. 45% vs. 40% for the old system. I've already reduced the 3 ton blower to it's lowest speed.
As a test I've captured the condensate in a bucket to measure humidity removal. The 3 ton system with piston metering pulled more humidity by day, less by night. The new TXV system pulls more humidity at night than day. Both units keep humidity about 45% at night.
Power Old unit consumed 3,000 to 3,500 watts depending on outside temperature. New unit consumes 1,800 to 2,500watts depending on outdoor temperature. Power use is on my in home wattmeter and includes blower consumption.
Delta T Old unit got about 18 degrees most of the time, day or night. New unit gets 14 degrees in day, 18 degrees at night. Keep in mind the blower speed was lowered when the new A/C was installed.
Cycle time Cycles were running about 6 minutes with the old unit, new unit runs about 8-10 minutes per cycle.
Noise New unit is WAY quieter, both units have 8 pole motors. Scroll compressor can barely be heard compared to the recip compressor of the old unit. With the new unit you can barely hear the fan, very impressed. Neighbor still has his 3 ton builder unit with the 1125 RPM fan and it's twice as loud as my old unit.

The coworker that helped me install it was impressed with how quiet the unit is and how much cooling it put out considering that it's only a 2 ton. He was a bit skeptical that the 2 ton could pull it off, but it's doing so with flying colors IMHO. So, believe the load calculations and don't fudge the input number to get the result you want. Yes the numbers may seem low, but they DO work !!!

Views: 1533

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Tom DelConte on December 10, 2013 at 8:09am

Nicely done Install !

Comment by Curt Kinder on September 9, 2012 at 9:41am

Absolutely agree - we routinely drop tonnage by 0.5 to 1.0 following a careful Man J, generally including a Blower Door test to nail down infiltration figure

Featured Forum Discussions

Too many BTU's. Too much horsepower?

Started by Steve in General Forum. Last reply by Eric Kjelshus 23 hours ago. 4 Replies

Stack/wind pressure and flow networks.

Started by Daniel James Grundy in Training. Last reply by Daniel James Grundy on Thursday. 5 Replies

BDT with vermiculite in hollow CMU walls?

Started by Brad Cook in General Forum. Last reply by John Nicholas on Thursday. 2 Replies

Strange IR Image

Started by Larry Nissman in General Forum. Last reply by Brad Cook Mar 9. 7 Replies

Videos

  • Add Videos
  • View All

Latest Activity

Eric Kjelshus replied to Steve's discussion Too many BTU's. Too much horsepower?
"Its more about run time with high RH removing, than to large over sized AC unit, in houses.  …"
23 hours ago
Sarah OConnell posted a blog post

Crowdsourcing for Innovation

Share Your Ideas!Novel Building Envelope Design for Increased Thermal PerformanceIn 2014, more than…See More
yesterday
Colin de Paor is now a member of Home Energy Pros
yesterday
Walter Ahlgrim replied to Steve's discussion Too many BTU's. Too much horsepower?
"The 5 ton system you have is not 500 hp racecar engines they are 500 hp truck engines. The duct…"
Friday
Daniel James Grundy replied to Daniel James Grundy's discussion Stack/wind pressure and flow networks.
"So I wanted to start with a basic who can help then go into more detail later. But yes find…"
Thursday
Daniel James Grundy replied to Daniel James Grundy's discussion Stack/wind pressure and flow networks.
"My tutor got back to me and while areas don't quite feel right a little to much assumptions…"
Thursday
Brennan Less replied to Daniel James Grundy's discussion Stack/wind pressure and flow networks.
"Daniel, I'm assuming you're trying to predict the airflows through the different openings…"
Thursday
Martin Newmark joined allen p tanner's group
Thumbnail

Energy Auditing Equipment for Sale, Trade or to Purchase

Discuss the pros and cons of the equipment you are interested in prior to purchase. Post equipment…See More
Thursday

Home Energy Pros

Welcome to Home Energy Pros – the unique digital community by and for those who work in the home energy performance arena.

Home Energy Pros was founded by the developers of Home Energy Saver Pro (supported by the U.S. Department of Energy) and brought to you in partnership with Home Energy magazine.  Home Energy Pros is sponsored by the Better Buildings Residential Network. Please honor our Guidelines

© 2017   Created by Lawrence Berkeley National Laboratory.   Powered by

Badges  |  Report an Issue  |  Terms of Service