Attic fans can suck air down flues causing spillage. Spillage can cause CO poisoning. Attic fans can't always be easily accessed or controlled. Read on:
While doing a comprehensive quality control visit last week, our Pure Energy Final Inspector noted that both the atmospheric draft water heater and atmospheric draft boiler failed these safety tests:
In addition to failing those tests, the negative pressure in the combustion appliance zone (CAZ) with reference to the outdoors was greater than allowed (the CAZ exceeded the maximum CAZ depressurization limit allowed) during the baseline and under the worst case conditions set up.
Upon further investigation, the Final Inspector found that, not only were the typical mechanical ventilation appliances making the CAZ negative, but the attic fan was on as well.
The attic was being ventilated to the outdoors by a typical attic fan installed in the roof. The pressure caused by the operating fan is sucking air out of the attic... and the house, and the CAZ, causing the CAZ to be under too great a negative pressure. Since every CFM of air that the fan exhausts has to come from somewhere, this negative pressure causes some of the make-up air to come down the flues rather than from the passive attic vents. The water heater and the boiler could not vent the flue gasses properly, and the fumes actually were being vented to the inside of the house. This is dangerous and unhealthy.
The reason the fan could suck air from the CAZ is because the attic was not fully separated from the house and from the basement as is required by the program and also from BPI.
So, not only does a leaky pressure boundary allow heated air to leak into the attic; moist air to leak into the attic; hot summer air to leak into the house; polluted air to leak into the house... but it also can impact the CAZ and cause CO and other pollutant poisoning.
Conclusions:
Recommendations for program administrators and technicians:
Comment
Comment by A. Tamasin Sterner on September 6, 2011 at 5:04pm
Comment by Ed Minch on September 6, 2011 at 4:42pm "Reverse static effect in the summer moves hot air from the attic into the living space."
I'm going to need an explanation of this.
Ed Minch
Comment by Paul Stevens on September 6, 2011 at 9:59am
Comment by Dale@EnergyWright on September 6, 2011 at 8:39am Nicely said, Tamasin. Yet articles promoting attic fan use are everywhere. They tout energy savings when the opposite is often true. You can even buy a solar-powered attic fan at Home Depot so you can feel green as you turn blue from CO poisoning.
Reverse static effect in the summer moves hot air from the attic into the living space. This convinces homeowners that the heat from the attic must be removed to keep the second floor cool. And as you pointed out, power-venting the attic can have dire consequences in the CAZ.
The August issue of Fine Homebuilding has a great article about roof/attic venting by Joe Lstiburek. No fans at all, he recommends a 60/40 ratio of soffit vents to ridge vents to ensure a subtle positive pressure in the attic.
Excellent thoughts on the attic fan. This is a great heads up for inspectors/auditors. The conclusions are well founded!
What about whole house fans? Is it a best practice to tell a home owner that by turning on their whole house fan they risk CO entering their home?
Thank you Tamasin for your 'always-excellent'' comments on these topics! David
Comment by David Meiland on September 5, 2011 at 8:56pm
Comment by A. Tamasin Sterner on September 5, 2011 at 10:35am
Comment by Joshua Lloyd on September 5, 2011 at 10:08am I have only come across this twice now, however one was just last week. The power attic ventilator was rated for 1100 CFM. I noticed it running when I was inspecting the attic, then when I was setting up Worst Case Draft I noticed air movement right at the draft hood and knew what was going on. So to show the home owner I kicked the water heater on and sure enough the water heater was not drafting at all, turn the fan off and it drafted fine. The attic ventilator was creating a depressurization of -3pa in the CAZ on it's own.
So needless to say he was not happy that the utility program I do audits for would not provide rebates until the fan was decommissioned. But I think I was able to explain to him why his attic was cooler now. It was sucking the conditioned air from his house into the attic, so it was actually increasing his cooling bills not only to cool his home, but the attic.
Home Energy Pros was founded by the developers of Home Energy Saver Pro (sponsored by the U.S. Department of Energy, under the American Recovery and Reinvestment Act) and brought to you in partnership with Home Energy magazine.
Joe Huang posted a discussion
Tom Delconte commented on Tom Delconte's blog post Lykans $29, Vampires $0 !
Joseph Lamy commented on Jim Gunshinan's blog post The Universe Is Made of Stories
J.C. Martel replied to J.C. Martel's discussion Disasters & sustainable energy
Judi Lyall joined allen p tanner's group
Judi Lyall replied to David Starrett's discussion I am looking for a good IR camera in the group Energy Auditing Equipment for Sale, Trade or to Purchase
Tom Maides commented on Jim Gunshinan's blog post The Universe Is Made of Stories© 2013 Created by Lawrence Berkeley National Laboratory.
You need to be a member of Home Energy Pros to add comments!
Join Home Energy Pros