As I had brought up years ago, ACCA's Manual S was in dire need of an update.  Written in 1995, Manual S Residential Equipment Selection was passed by with huge technical and efficiency strides within the HVAC industry.  Think about it: ECM Motors were in their infancy, condensing furnaces were still prone to failures, and variable refrigerant flow was far from mainstream in the U.S.  All addressed in the updated Manual S! I have to say, their committee did a thorough job addressing updates to a process that is essential to system design and a code requirement in most of our country!  I highly recommend HVAC Sales Staff, System Designers, and Building Analysts purchase a copy of the new text, but in the meantime here is a teaser:

1.  Multi-Stage Central A/C: can be sized between .90 and 1.20 of the total building load.  This additional 5% of capacity vs. 1995 becomes increasingly important as homes get tighter and Sensible Heat Ratios rise.  Higher airflow to handle the increase in sensible loads lends to higher capacities.

2.  Variable Capacity Central A/C: can be sized between .90 and 1.30 of the total load.  See #1 for sensible capacity reasons, but variable capacity equipment is great for handling high latent capacities when operating on part load days as well.

3.  Cold Climate Heat-Pumps: can be sized to the total cooling building load + 15,000 btu/hr maximum.  This goes for single-stage, two-stage, and variable capacity equipment.  For mini-split heat-pumps, this 15K is above the total block load.

4.  Heat Pump Supplemental Electric Heaters: can be no larger than 5KW if the heat load is < 15,000 btu/hr.

5.  Fossil Fuel Burning Furnaces and Boilers: can be sized between 1.0 and 1.40 of the total heat load.  Ok, this isn't a change, just thought it was important to know!  If installing a furnace that needs a larger blower for cooling, maximum is now 2.0.

     Loaded with up to date examples, the new Manual S is far from a dust collector.  A great reference manual, but lets just hope it is not for another two decades like it's predecessor...but don't take my word for it!

Excess Air

Views: 246

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Eric Kjelshus on August 28, 2014 at 8:33am

I run loads each day.  BUT my completion does not,    I see so much over sizing  last job was needing 34,000 and he put in 120,000 BTU's ( the box fit)  I took out 1/2 the burners so the BTU fit the duct work and closer to the building.    My grand Pa would size 3 times needed or down to -40  so you could open the windows in bedrooms 8" to get "air" at night.   in the 1880 the gas was made from coal and was very high CO  when would burn,  some  Lights would be gas and CO in the building go high so would open window's to vent the home.    Gas was so cheap that was not metered  just so much a yr.

Welcome to Home Energy Pros

Welcome to Home Energy Pros – the unique digital community by and for those who work in the home energy performance arena.

Home Energy Pros was founded by the developers of Home Energy Saver Pro (supported by the U.S. Department of Energy) and brought to you in partnership with Home Energy magazine.  Home Energy Pros is sponsored by the Better Buildings Residential Network. Please honor our Guidelines

Featured Blogs

Seeking Innovation in Roofing Systems

Posted by Sarah OConnell on May 12, 2017 at 9:47am 0 Comments

Oak Ridge National Lab has partnered with GAF to host a technology challenge on roofing systems.  The challenge is part of the online crowdsourcing site, JUMP, and aims to identify innovation solutions for ensuring energy efficient and durable…

Continue

Top tips for maintaining an evaporative cooler

Posted by Kobus Niemand on May 4, 2017 at 3:30am 0 Comments

Evaporative coolers, also known as swamp coolers have become a top choice for anyone looking for an alternative cooling solution from their home or office. In the past, evap cooler technology was limited for use in large operations that have easy…

Continue

Congratulations to the 2017 Race to Zero Winners!

Posted by Home Energy Magazine on May 9, 2017 at 6:56am 0 Comments

The Ryerson University and University of Toronto team topped the …

Continue

Connecting the Dots: Real Estate and Home Performance

Posted by Home Energy Magazine on May 9, 2017 at 6:50am 5 Comments

A new type of conversation between REALTORS® and their clients is changing the real estate industry before our eyes. As homebuyers browse Zillow listings and spend…

Continue

Latest Activity

Horace Douglas Hunt, Jr. posted a status
"Still looking to purchase a used RetroTec blower door - complete system. Anyone have something available?"
5 hours ago
Sean Lintow Sr replied to Luis Hernandez's discussion Solar panel leasing
"Sorry but no, not that big of a thing up here Biggest issue I see for most is everyone grid ties…"
22 hours ago
Helen Best commented on Helen Best's blog post This Might Be the Most Water-Efficient Shower Head Ever Invented
"Nebia is now accepting pre-orders on their website to ship late this summer."
yesterday
Michael Dunseith replied to Michael Dunseith's discussion $ SALE : Like New Video Borescope/Wireless Inspection Camera in the group Energy Auditing Equipment for Sale, Trade or to Purchase
"SOLD"
Friday

© 2017   Created by Lawrence Berkeley National Laboratory.   Powered by

Badges  |  Report an Issue  |  Terms of Service