Thompson SFP House Detail

Cross-section of frost-protected shallow foundation for 12" truss-wall framing system.

Views: 407

Comment

You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Robert Riversong on September 6, 2012 at 10:52am

I forgot to include the BSC link: http://www.buildingscience.com/documents/insights/bsi-003-concrete-...

The other consideration is the very high global warming potential of XPS, for which a new analysis by Alex Wilson and friends shows becomes worse over its lifetime at more than about R-15-20.

http://www2.buildinggreen.com/blogs/insulation-keep-us-warm-not-war...

http://www2.buildinggreen.com/content/global-warming-potential-insu...

Comment by Robert Riversong on September 6, 2012 at 10:47am

David,

This represents a balance between minimizing heat loss from a radiant slab into the ground and allowing sufficient downward heat loss to maintain the foundation as frost-proof (as well as moderately earth-coupling the house to the ground in the event of prolonged periods without supplemental heat, such as power outages or winter vacations).

Most proponents of superinsulated building would put more than R-10 under the slab, particularly a heated slab, with Passive House folks sometimes using as much as R-40. So I consider 2" XPS a minimum for this application, which includes FPSF, radiant and solar thermal mass slab.

Comment by David Williams on September 6, 2012 at 9:48am

Extruded (of course).  I also like the way that you achieve the R15 edge requirement.  I have modeled energy loss comparing 2" XPS with 1" XPS in well drained + soils climate zone 6. and have reservations about the added cost of 2" under the slab.  Knowing that you only get 1 shot at getting this right, I wonder what you thoughts are and where you would draw the line between 1" & 2".

Can you offer a link to the Building Science Corp reference?

Comment by Robert Riversong on September 6, 2012 at 9:18am

David,

Yes, that should have been noted in the section. I use a Tu-Tuf 4 mil laminated vapor barrier that is designed for sub-slab applications and is highly tear-resistant. All seams are taped, as well as all seams of the XPS (not EPS) insulation board.

It is a bad idea to put any "reservoir" layer of sand between the vapor barrier and the slab - Building Science Corp addresses this - as it is likely to create moisture problems. The slab finisher loves it because he can power trowel the slab and get home to his Budweiser sooner, but a vapor barrier does not cause slab cracking or curling.

Comment by David Williams on September 6, 2012 at 8:56am

Do you have a moisture barrier below the slabs' EPS?  I have found that a 1" layer of sand, placed over the EPS helped to protect both the insulation and vapor barrier.  This may have also provided some amount of moisture control during the curing phase.  I have had concrete contractors exclaim that slabs poured over EPS are very prone to cracking because of the way the the moisture escapes form the curing slab.

I have not had these cracking issues, on the radiant heated slabs that I have done over the past 30 years, but I have seen them in slabs that did not have proper edge insulation. 

Home Energy Pros

Home Energy Pros was founded by the developers of Home Energy Saver Pro (sponsored by the U.S. Department of Energy,) and brought to you in partnership with Home Energy magazine.

Latest Activity

Laurie DiDonato posted an event
Thumbnail

HERS Rater Training at Online and United Illuminating Company

June 1, 2015 at 9am to June 18, 2015 at 4pm
The Northeast HERS Alliance is offering a NEW Hybrid Rater training course designed to prepare…See More
52 minutes ago
Paul Raymer's blog post was featured

Shades of Gray in Residential Construction Morality

I was called in to perform a last minute duct test for a modular home builder.  He was all in a…See More
1 hour ago
Charlie Hewitt's blog post was featured

Residential Electric Load Disaggregation

“What gets measured gets managed” is a quote often attributed to the venerable management expert…See More
1 hour ago
Paul Haasz joined Evan Mills's group
Thumbnail

Home Energy Ratings

Calculating them; visualizing them; explaining them; selling them .... there is a lot to discuss…See More
20 hours ago
Paul Haasz joined James Sayers's group
Thumbnail

Marketing Energy Efficiency

Sharing ideas, tools and examples of promoting energy efficiency to consumersSee More
20 hours ago
Paul Haasz joined allen p tanner's group
Thumbnail

Energy Auditing Equipment for Sale, Trade or to Purchase

Discuss the pros and cons of the equipment you are interested in prior to purchase. Post equipment…See More
20 hours ago
Paul Haasz joined Leslie McDowell, BPI's group
Thumbnail

Building Performance Institute (BPI)

BPI is the nation's premier standards development, quality assurance and credentialing organization…See More
20 hours ago
Paul Haasz joined Sean Lintow Sr's group
Thumbnail

Best Practices (Residential)

Best Building, Retrofitting, or even Auditing Practices - what are they, what should change, what…See More
20 hours ago

© 2015   Created by Lawrence Berkeley National Laboratory.

Badges  |  Report an Issue  |  Terms of Service