Dense Packed Ducts

Return ducts used floor/ceiling joist and balloon frame wall cavities for return air. Once the walls were insulated the furnace suffocated and pulled all return air from the basement. The worst case CAZ was -12.3pa causing the furnace to backdraft and the basement to reach 97ppm of CO.

Views: 238


You need to be a member of Home Energy Pros to add comments!

Join Home Energy Pros

Comment by Joseph J. Ilacqua on November 30, 2012 at 11:50am

Yes in my location in upstate NY this is a common practice. Even more common while dense packing tuck under garage ceilings. Be carefull and beware. That is why we do constant pre and post job inspections. Sometimes even with a great inspection these can be missed. Learn from someones else's mistakes and try not to make the same one.


  • Add Videos
  • View All


Latest Activity

Diane Jackson posted a photo

"Drive Home"

Addison Homes spent a fun day with a film crew from the National Association of Home Builders. We…
3 hours ago
Paul Raymer posted a blog post

Healthy Home Evaluator Training

Fall River, MA     October 13, 2016…See More
7 hours ago
Diane Chojnowski updated an event

Better homes video series at Seventhwave

October 24, 2016 to January 26, 2017
9 hours ago
Profile Iconseoeleczo and Parfait Pouliotte joined Home Energy Pros
9 hours ago
Amber Vignieri's blog post was featured
9 hours ago
Sarah Holloway's blog post was featured
9 hours ago
Quinn Korzeniecki added a discussion to the group Building Performance Institute (BPI)

Creating a Home that is Right for You and Your Family

Today's prospective homeowners have the option of either buying an existing home or building one…See More
10 hours ago
Steven Lefler commented on Paul Scheckel's blog post Gas vs Induction Cooking Energy Comparison
"No one in government wants you to disconnect from the grid. All electric houses (ON Gird) with Time…"

© 2016   Created by Lawrence Berkeley National Laboratory.   Powered by

Badges  |  Report an Issue  |  Terms of Service